PDF

FT2DT2H2

Thermocouple cable with glass-fibre insulation and sheath, tinned copper braid shield

 

  1. Conductor
  2. Insulation
  3. Sheath
  4. Shield

 

APPLICATION: Extension and compensating cables for thermocouples.

 

INSTALLATION: For fixed or mobile installation in dry environments at high temperature, in the absence of tensile stresses and forced displacements, laying in catenary with repeated cycles is not allowed. The cable (fixed installation) is suitable for installation in pipes, on plaster and closed installation ducts. The copper braid protects the cable against electromagnetic interference.



FEATURES DESCRIPTION STANDARDS
Conductors: type T : +Cu -CuNi
type J : +Fe -CuNi
type E : +NiCr -CuNi
type K : +NiCr -NiAl
type W : +Fe -CuNi
type S and R : +Cu -CuNi
type B : +Cu -Cu
 
Insulation: braid of glass-fibre  
Cores colour: see thermocouple table  
Sheath: braid of glass-fibre, oval shape  
Sheath colour: see thermocouple table  
Shield: braid of annealed tinned copper  
Flame retardant:   CEI EN 60332-1-2
Working temperatures: -60 °C ÷ +250 °C  
Bending radius: Ø x 7,5  

 

TYPE
N° x mm2
MEDIUM Ø OUTER
mm
MEDIUM WEIGHT
kg/km
PRODUCT CODE
2x0,35 3,5x2,3 23 B4702035(*)SR
2x0,5 4,5x2,8 33 B4702050(*)SR
2x0,8 5,0x3,0 39 B4702080(*)SR
2x1 5,2x3,1 46 B4702100(*)SR
2x1,3 5,6x3,3 55 B4702130(*)SR
2x1,5 5,8x3,4 66 B4702150(*)SR

(*) Add J for J-W-T-S calibration, K for K calibration

 

Berica Cavi S.p.A. reserves the right to change all information on the website without giving prior notice to customers and / or users