RG 59 B/U 75 Ω FR (PH30)
Coaxial cables for video signal transmission, fire resistant, flame retardant, halogen free.
|
 |
- Conductor
- Insulation
- Flame protection
- Shield
- Inner sheath
- Outer sheath
|
|
APPLICATION: Suitable for the connection between camera and recorder in television closed-circuit systems when there is the need to ensure the transmission of the signal even in the presence of fire
INSTALLATION: For fixed indoor installation, without protection or in pipes, conduits and simillar closed systems.
|
| FEATURES |
DESCRIPTION |
STANDARDS |
| Conductor: |
annealed red copper 0,65 mm |
|
| Insulation: |
low density polyethylene LDPE |
|
| Insulation: |
ceramifiable silicone rubber |
|
| Flame protection: |
glass-fibre tape |
|
| Shield: |
double braid of annelead red copper |
EN 50117-2-4 screening cl.A |
| Inner sheath: |
LSZH compound |
|
| Outer sheath: |
LSZH compound, M1 quality |
CEI EN 50363 |
| Outer sheath colour: |
red RAL 3000 |
|
| Flame retardant: |
|
CEI EN 60332-1-2 |
| Halogen free: |
(< 0,5 mg/g - 0,5%) |
CEI EN 50267-2-1/2 - IEC 60754-1/2 |
| Low smoke emission: |
(trasmittance > 60%) |
CEI EN 61034-2 |
| Fire resistant: |
duration 30 min. at temperature of 830 °C (- 0 ÷ + 40 °C) |
CEI EN 50200 |
| Fire resistant: |
(E30) |
DIN VDE 4102-12 |
| Fire resistant: |
duration 180 min. at temperature of 750 °C (FE 180) |
IEC 60331-21 - VDE 472-814 |
| Fire resistant: |
|
BS 6387 Cat. CWZ |
| Capacitance: |
of the order of 75 nF/km |
|
| Inductance: |
of the order of 0,50 mH/km |
|
| Testing voltage: |
7 kVac |
|
| Max working temperature: |
90 °C |
|
| Min. installation temperature: |
0 °C |
|
| Bending radius: |
Ø x 14 |
|
| Printing: |
BERICA CAVI S.P.A. ITALY Formazione FR Year/Lot |
|
|
|
| ATTENUATION |
| MHz |
0,5 |
1 |
5 |
10 |
100 |
300 |
| dB/100 m |
0,7 |
1,1 |
2,6 |
3,6 |
14,3 |
31,6 |
|
|
| TYPE |
MEDIUM Ø OUTER mm |
MEDIUM WEIGHT kg/km |
PRODUCT CODE |
| RG 59 B/U FR |
10,3 |
154,0
|
B40RG59FR |
|
Berica Cavi Spa reserves the right to edit all the information on the website without providing prior notice to customers and / or users