PDF

EUROSAFE FLEX 0,6/1 kV (FE180) (PH120)

Cables for fire detection sensors, Al/Pet tape screen, fire resistant,
fire retardant, halogen free.

 

  1. Conductor
  2. Flame protection
  3. Insulation
  4. Assembling
  5. Drain wire
  6. Screen
  7. Sheath

 

APPLICATION: Suitable for the connection between the sensors and the control unit of the fire detection systems when it is required special characteristics such as: fire resistance, low smoke emission, low toxic and corrosive gases emission and the absence of halogens.

 

INSTALLATION: For fixed indoor and outdoor installation. They can be installed in cable trays, pipes, conduits and similar systems. Also for indirect burial.



FEATURES DESCRIPTION STANDARDS
Conductors: annealed red copper Cl.5 CEI EN 60228 (Tab. 9)
Flame protection: mica-glass tape  
Insulation: Special LSZH compound CEI EN 50363
Cores colour: red and black CEI UNEL 00722 - HD 308
Assembling: Pet tape  
Drain wire: annealed tinned copper  
Screen: Al/Pet tape  
Sheath: LSZH compound, M1 quality CEI EN 50363
Sheath colour: red RAL 3000  
Fire retardant:   CEI EN 60332-3-24
Flame retardant:   CEI EN 60332-1-2
Halogen free: (< 0,5 mg/g - 0,5%) CEI EN 50267-2-1/2 - IEC 60754-1/2
Low toxic gases emission: (toxicity index < 2%) CEI 20-37/4-0
Low smoke emission: (trasmittance > 60%) CEI EN 61034-2
Fire resistant: duration 120 min. at temperature of 830 °C (- 0 ÷ + 40 °C) CEI EN 50200 (PH120)
Fire resistant: duration 180 min. at temperature of 750 °C (- 0 ÷ + 50 °C) CEI IEC 60331-21 (FE180)
DC resistance: according to CEI EN 60228 (Tab. 9)
Rated voltage Uo/U: 0,6/1 kV  
Max voltage: 1,2 kV  
Testing voltage: 4 kV  
Max working temperature: 70 °C  
Short-circuit temperature: 160 °C  
Min. installation temperature: 0 °C  
Bending radius: Ø x 14  
Max standard twisting (2x cable): ≥ 10 twist/meter  
Printing: BERICA CAVI S.P.A. ITALY EUROSAFE FLEX Type 0,6/1 kV CEI EN 50200 (PH120) (FE180) IEC 60332-3-24 CE Year/Lot  
TYPE
N° x mm2
MEDIUM Ø OUTER
mm
MEDIUM WEIGHT
kg/km
PRODUCT CODE
2x1 8,1 85 to be defined
2x1,5 8,7 100,0 to be defined
2x2,5 9,9 132 to be defined

 