APPLICATION: Suitable for energy transport and the transmission of signals and controls where a certain level
of mechanical protection (rodents-termites) is required.In the most risky environments in the
event of a fire, such as health facilities, entertainment venues and entertainment in general,
gyms and sports centers. Hotels, guest houses, motels, villages, tourist residences - hotels.
Schools of every order, grade and type. Exhibitors and / or retailers. Companies and offices
with more than 300 people present; Libraries and archives, museums, galleries, exhibitions and
exhibitions. Buildings intended for civil use, with a fire height of more than 24m. (Average Risk)
INSTALLATION: For fixed indoor and outdoor installation even in wet environments. They can be installed on
wall and metal structures, on platforms, pipes, conduits and similar systems. Cable for direct
and indirect burial.
|
| FEATURES | DESCRIPTION | STANDARD |
| Conductors: |
annealed red copper cl.5 |
CEI EN 60228 (Tab. 9) |
| Insulation: |
LSZH compound, G16 quality |
CEI EN 50363 |
| Cores colour: |
|
CEI UNEL 00722 - HD 308 |
| Inner sheath: |
Thermoplastic compound |
CEI EN 50363 |
| Armour: |
Steel wire with steel tape wrapped helically |
|
| Outer sheath: |
Thermoplastic compound, R16 quality |
CEI EN 50363 |
| Outer sheath colour: |
Grey RAL 7035 |
|
| Low halogens emission: |
(< 22%) |
CEI EN 50267-2-1/2 - IEC 60754-1/2 |
| DC resistance: |
According to |
CEI EN 60228 (Tab. 9) |
| Current capacity: |
|
CEI UNEL 35024/1 - CEI UNEL 35026 |
| Rated voltage Uo/U: |
0,6/1 kV |
|
| Max. voltage: |
1,2 kV |
|
| Testing voltage: |
4 kV |
|
| Max working temperature: |
90 °C
|
|
| Short-circuit temperature: |
250 °C |
|
| Min. installation temperature: |
0 °C |
|
| Bending radius: |
Ø x 14 |
|
| Max standard twisting (2x cable): |
≥ 10 twists/meter |
|
| REGULATION (UE) 305/2011 |
| System AVCP : |
1+ |
EN 50575:2014 + A1:2016 |
| Classification : |
Cca-S3,d1,a3 |
UNI EN 13501-6 |
| Cca : |
Heat release and flame spread (FS ≤ 2m) |
EN 50399 |
| s3 : |
Smoke production (not s1 or s2) |
EN 50399 |
| d1 : |
No flaming droplets/particles persisting longer than 10 s |
EN 50399 |
| a3 : |
Gas acidity (not a1 or a2) |
EN 50267-2-3 |
|
Flame propagation (H ≤ 425 mm) |
EN 60332-1-2 |
| Printing: |
BERICA CAVI S.P.A. ITALY FG16OFR16 0,6/1 kV Cca-S3,d1,a3 CE Type- Year/Lot - 00000 m |
|
|
|
TYPE N° x mm2 | MEDIUM Ø OUTER mm | MEDIUM WEIGHT kg/km | PRODUCT CODE |
| 2x1,5 | 12,0 | 285 | B20C02150 |
| 3G1,5 | 12,5 | 311 | B20C03150 |
| 4G1,5 | 13,4 | 349 | B20C04150 |
| 5G1,5 | 14,3 | 397 | B20C05150 |
| 7G1,5 | 15,2 | 460 | B20C07150 |
| 10G1,5 | 18,4 | 598 | B20C10150 |
| 12G1,5 | 19,2 | 678 | B20C12150 |
| 16G1,5 | 21,1 | 818 | B20C16150 |
| 19G1,5 | 22,1 | 902 | B20C19150 |
| 24G1,5 | 24,9 | 1093 | B20C24150 |
| 2x2,5 | 12,8 | 329 | B20C02250 |
| 3G2,5 | 13,4 | 369 | B20C03250 |
| 4G2,5 | 14,4 | 420 | B20C04250 |
| 5G2,5 | 15,4 | 476 | B20C05250 |
| 7G2,5 | 16,7 | 579 | B20C07250 |
| 10G2,5 | 20,2 | 772 | B20C10250 |
| 12G2,5 | 21,1 | 856 | B20C12250 |
| 16G2,5 | 23,4 | 1049 | B20C16250 |
| 24G2,5 | 27,4 | 1405 | B20C24250 |
| 2x4 | 14,2 | 407 | B20C02400 |
| 3G4 | 14,8 | 407 | B20C02400 |
| 4G | 16,1 | 542 | B20C04400 |
| 5G4 | 17,4 | 616 | B20C05400 |
| 2x6 | 15,7 | 497 | B20C02600 |
| 3G6 | 16,4 | 497 | B20C02600 |
| 4G6 | 17,7 | 664 | B20C04600 |
| 5G6 | 19,3 | 783 | B20C05600 |
| 2x10 | 17,8 | 658 | B20C021000 |
| 3G10 | 18,9 | 772 | B20C031000 |
| 4G10 | 20,7 | 931 | B20C041000 |
| 5G10 | 22,4 | 1087 | B20C051000 |
| 2x16 | 20,6 | 897 | B20C021600 |
| 3G16 | 21,7 | 1052 | B20C031600 |
| 4G16 | 23,8 | 1276 | B20C041600 |
| 2x25 | 24,2 | 1225 | B20C022500 |
| 3G25 | 25,6 | 1466 | B20C032500 |
| 4G25 | 28,1 | 1774 | B20C042500 |
| 3x35+1x/G25 | 32,1 | 1800 | B20C043500 |
| 3x50+1x/G25 | 5,2 | 2420 | B20C045000 |
|